Main Technical Parameters
Power supply voltage: 220VAC, 380VAC,
Input signal: 4 ~ 20 mADC; 1VDC~5VDC; pulse and level signal; fieldbus signal,
output signal:
Valve position feedback signal from 4 to 20 mADC,
Valve position status signal no active dry contact contact capacity DC30V / 5A AC250V / 5A,
State alarm signal no active dry contact contact capacity DC30V / 5A AC250V / 5A,
Control accuracy (basic error): ± 0.5%,
Return difference: 0.5%
Dead zone: 0.5%
Rated pressure of the hydraulic cylinder: 12MPa
Used temperature: standard type-30℃ ~80℃, low temperature type: -40℃ ~80℃
Protection level: IP66, IP67
Explosion-proof grade: ExdIIBT4, ExdIICT4
Hydraulic oil: L-HV 32 # low-temperature anti-wear hydraulic oil (Northern region: use hydraulic oil below low temperature- 30℃) Standard output torque and running time (full stroke), see Table 1