Main Technical Parameters
External power supply: three-phase 380VAC- 10%/+10%; 50Hz ± 1%;
Single phase 220VAC- 15%/+10%; 50Hz ± 1%
Remote control power supply: internally supplied non regulated 24VDC power output, used to drive passive switching input.
Insulation level of motor: F level, switch type S2-15min, 60 times/hour;
Adjustable S4-50% load connection rate, 1200 times/hour.
Design life: 10000 times of rated torque opening for switch type cyclic testing.
Adjust the cycle test 500000 times to open at 50% of the rated torque.
Environmental temperature: -30~+70
Relative humidity: ≤ 95%
Protection level: IP68
Explosion proof level: Ex db Ⅱ C T4 Gb
Dust explosion-proof level: Ex tb III C T135 ℃ Db
Analog output: 4-20mADC, load resistance ≤ 750 Ω
Switching output: 5 sets of relay output contacts with contact capacities of 5A 250VAC and 5A 30VAC
The fieldbus (optional) supports MODBUS, PROFIBUS, CANOPEN, HART, RS485, etc.
Output torque: integrated series 60N. m~1000N. m, equipped with gearbox series 1100N. m~2500N. m
Output angle: 0-90 degrees
Connection part: Adopt flange connection according to the national standard GB/12223-2005.
Appearance: The surface protection adopts electrostatic spray molding process.
The surface undergoes high-temperature solidification to form a hard coating film;
It has strong wear resistance, corrosion resistance, salt spray resistance, and other properties.